The power circuit fuse is mainly used to protect low-voltage electrical equipment in the production process and daily life of industrial and mining enterprises. Because it is used in different electrical equipment, the selection principles of its capacity and size vary greatly. In practice, it must be selected and configured in strict accordance with the regulations.
Applied to household appliances: the fuse used for overcurrent or overload protection of household appliances. Generally, there is no independent overload protection for household electricity, and only the fuse is set instead. Its configuration principle is to place it according to 1.05~1.15 times of the total current when all household appliances are used.

Instantaneous short circuit protection for low-voltage motors: for light-load starting or short starting time, such as starting time less than 3s or fan (fan) motors, it shall be configured according to (4-5) times of the rated current of the motor; For motors with a starting time of 4s to 8s, or with heavy loads such as water pumps, since the starting current is up to about 6 times of the rated current, the size of the configured fuse is set as (5~6) times of the rated current of the motor; For motors with a starting process of more than 8s or longer and frequent starting, the fuse shall be configured as (5-7) times of the rated current of the motor.
For multiple small-capacity motors sharing line short circuit protection: for multiple small-capacity motors sharing line fuse size configuration, it is set according to the sum of (1.5~2.5) times of the rated current of the largest motor and the rated current of all the remaining motors.